Research Article
Generator Set Loading Analysis on The Radio Republik Indonesia Building in Tarakan City, North Kalimantan Province
@INPROCEEDINGS{10.4108/eai.23-11-2022.2341595, author={Martinus Herbertus Eman and Nurliya Nurliya and Ismit Mado}, title={Generator Set Loading Analysis on The Radio Republik Indonesia Building in Tarakan City, North Kalimantan Province }, proceedings={Proceedings of the International Conference on Sustainable Engineering, Infrastructure and Development, ICO-SEID 2022, 23-24 November 2022, Jakarta, Indonesia}, publisher={EAI}, proceedings_a={ICO-SEID}, year={2023}, month={12}, keywords={genset load capacity ecodial advance tarakan city}, doi={10.4108/eai.23-11-2022.2341595} }
- Martinus Herbertus Eman
Nurliya Nurliya
Ismit Mado
Year: 2023
Generator Set Loading Analysis on The Radio Republik Indonesia Building in Tarakan City, North Kalimantan Province
ICO-SEID
EAI
DOI: 10.4108/eai.23-11-2022.2341595
Abstract
The study was conducted to compare the capacity of the generator set installed in the Radio Republic of Indonesia Building in Tarakan City with the Ecodial Software calculation and determine the capacity and voltage of the generator, the safety rating, and the appropriate cross-sectional cable for the generator to supply the installed load. To determine the capacity and voltage, data collection of equipment is carried out. Ecodial Advance Calculation 4.7 software is used to simulate a single line diagram, by entering the load data and the power factor will be known. The simulation results of Ecodial Advance Calculation 4.7 obtained the power capacity of the generator set of 65 kVA, 380 V, 3 phase with a power factor of 0.8. The result of calculating the total power load on the main building of RRI Tarakan is 22,632 Watt which consists of 2 floors. For the 1st floor the load power is 11,281 Watt and for the 2nd floor the load power is 11,351 Watt. With a maximum KHA of 75 A for the 2nd floor design in the HR room with the type of security iC60N. For the cable, it is recommended to use a cable containing copper with a size of 1x6 Cu and 1x25Cu with a current-carrying cable of 63 A and 75 A.