Research Article
Combination of Single Tuned Filter and Double Tuned Filter to Reducing Current Harmonics
@INPROCEEDINGS{10.4108/eai.16-11-2019.2293269, author={Azmi Rizki Lubis and Marwan Affandi and Mustamam Mustamam}, title={Combination of Single Tuned Filter and Double Tuned Filter to Reducing Current Harmonics}, proceedings={Proceedings of the the 3rd Annual Conference of Engineering and Implementation on Vocational Education, ACEIVE 2019, 16 November 2019, Universitas Negeri Medan, North Sumatra, Indonesia}, publisher={EAI}, proceedings_a={ACEIVE}, year={2020}, month={3}, keywords={harmonic single tuned filter double tuned filter}, doi={10.4108/eai.16-11-2019.2293269} }
- Azmi Rizki Lubis
Marwan Affandi
Mustamam Mustamam
Year: 2020
Combination of Single Tuned Filter and Double Tuned Filter to Reducing Current Harmonics
ACEIVE
EAI
DOI: 10.4108/eai.16-11-2019.2293269
Abstract
This paper presents the results of the analysis of a combination of a single tuned filter (STF) and a double tuned filter (DTF) to reducing harmonic currents in a three-phase system. From the research that has been done, obtained significant results in reducing the current harmonic content in the three-phase system. THDi from 25.49% reduced to 14.84% and the 5th harmonic content is 21.69% reduced to 13.45%, the 7th harmonic content is 10.26% reduced to 4.63%, the 11th harmonic content is 6.42% reduced to 2.33%, and the 13th harmonic content is 4.46 %% reduced to 1.32%.
Copyright © 2019–2024 EAI