About | Contact Us | Register | Login
ProceedingsSeriesJournalsSearchEAI
Smart Grid and Innovative Frontiers in Telecommunications. 7th EAI International Conference, SmartGIFT 2022, Changsha, China, December 10-12, 2022, Proceedings

Research Article

Simulation Research on the Ground Resistance Measurement of the Tower with Clamp Meter Considering the Influence of the Tower Foundation

Cite
BibTeX Plain Text
  • @INPROCEEDINGS{10.1007/978-3-031-31733-0_38,
        author={Zoujun Wang and Wenbo Li and Huashi Wu and Jiafeng Chen and Hailiang Lu},
        title={Simulation Research on the Ground Resistance Measurement of the Tower with Clamp Meter Considering the Influence of the Tower Foundation},
        proceedings={Smart Grid and Innovative Frontiers in Telecommunications. 7th EAI International Conference, SmartGIFT 2022, Changsha, China, December 10-12, 2022, Proceedings},
        proceedings_a={SMARTGIFT},
        year={2023},
        month={5},
        keywords={Clamp meter method Tower foundation p ground resistance},
        doi={10.1007/978-3-031-31733-0_38}
    }
    
  • Zoujun Wang
    Wenbo Li
    Huashi Wu
    Jiafeng Chen
    Hailiang Lu
    Year: 2023
    Simulation Research on the Ground Resistance Measurement of the Tower with Clamp Meter Considering the Influence of the Tower Foundation
    SMARTGIFT
    Springer
    DOI: 10.1007/978-3-031-31733-0_38
Zoujun Wang1,*, Wenbo Li1, Huashi Wu2, Jiafeng Chen3, Hailiang Lu3
  • 1: StateGrid Hunan Electric Power Company Limited Research Institute
  • 2: Guangdong Power Grid Corporation
  • 3: School of Electrical and Automation, Wuhan University
*Contact email: 513474070@qq.com

Abstract

The grounding resistance of the tower is the main parameter to measure the grounding safety performance of the tower. As a commonly used method of measuring the grounding resistance of the tower, the clamp meter method has certain errors in the measurement principle. Based on the measurement principle of the clamp meter method, the artificial grounding device, tower foundation, transmission line tower and lightning protection wire are modeled and simulated, and the influence of different factors on the error of the clamp meter method measurement of the ground resistance of the tower is studied. The calculation results show that the change of soil resistivity has the most obvious influence on the calculation results. The higher the soil resistivity is, the coefficient of transformation between the measurement results of clamp tab. Method and the actual value gradually decreases. In the case of multi base tower grounding, the measured transformation ratio coefficient will be smaller than that in the case of single base tower grounding due to the shunt of tower lightning line parallel branch; The shorter the span between towers or the lower the height of towers, the smaller the parallel equivalent impedance of tower lightning line branches and the smaller the transformation ratio coefficient.

Keywords
Clamp meter method Tower foundation p ground resistance
Published
2023-05-26
Appears in
SpringerLink
http://dx.doi.org/10.1007/978-3-031-31733-0_38
Copyright © 2022–2025 ICST